Sensing technologies
• CO₂ — Non-Dispersive Infra-Red (NDIR) is the de-facto standard for accuracy (±30–50 ppm + 3 % rdg, 400–5 000 ppm). Avoid MOS “eCO₂” parts if you need real ppm values.
• Humidity — capacitive polymer sensors (SHT3x/BME280 class, ±2 % RH).
• Temperature — band-gap or thermistor inside the RH device (±0.3 °C typical).
Zigbee layer
• Use Zigbee 3.0 or at least HA 1.2 application profile.
• Mandatory clusters
– 0x0402 Temperature Measurement
– 0x0405 Relative Humidity
– 0x040D Carbon Dioxide Concentration (ZCL v8+) or manufacturer specific if older firmware.
• Reporting: configure periodic (5–15 min CO₂, 1–5 min T/RH) or delta-triggered (±50 ppm / ±0.5 °C / ±2 % RH).
Power & topology
• Battery-powered units act as End-Device → 6–12 month life if CO₂ sample interval ≥5 min and sensor duty-cycled.
• USB/mains units can sample every 60 s, serve as Zigbee Routers and improve mesh reliability.
Calibration & accuracy
• Automatic Baseline Calibration (ABC) assumes the space hits ~420 ppm each 7–8 days – disable in constantly occupied rooms.
• Offer manual “fresh-air” calibration option or factory 2-point calibration.
• Altitude and RH compensation recommended (built-in on SCD4x, SenseAir-S8).
Integration & firmware
• Home Assistant: ZHA recognises Titan TPZRCO2HT-Z3 natively; Zigbee2MQTT supports Titan, Heiman, ALab (via external converter).
• SmartThings / Hubitat: custom DTH/driver may be required for cluster 0x040D.
• OTA upgrade (Image Notify cluster 0x0019) desirable for long-term support.
Mechanical & placement
• Mount 1–1.5 m above floor, away from exhalation jets, HVAC vents, direct sun.
• For schools/offices place one sensor per 30–40 m²; cross-check with reference instrument annually.
Model | CO₂ range | Power | Router? | Price (USD) | HA support |
---|---|---|---|---|---|
Titan TPZRCO2HT-Z3 | 0-5 000 ppm | 2×AA | No | 135 | Native |
Heiman/GAOTek | 0-5 000 ppm | USB | Yes | 55-70 | Z2M |
Tuya “Air Box” | 0-5 000 ppm | USB | Yes | 35-50 | Z2M, ZHA (quirk) |
ALab (SenseAir-S8) | 0-5 000 ppm | USB | Yes | 80 | Z2M (ext conv) |
Selection checklist
• NDIR sensor with stated accuracy ±(30 ppm + 3 %).
• Zigbee 3.0 certified or well-documented fingerprint.
• Field calibration option.
• Router capability if mains-powered.
Commissioning steps
1) Hold the reset/pair button 5 s → LED blinks.
2) Put coordinator in pairing mode; verify clusters exposed.
3) Configure reporting intervals and thresholds to balance traffic vs. responsiveness.
4) Place sensor, wait ≥30 min for thermal equilibrium.
Troubleshooting
• Drop-outs → add mains Zigbee router midway; verify RSSI > –70 dBm.
• Drifting low readings → disable ABC, perform outdoor calibration.
• Battery drain → increase measurement interval to ≥10 min, ensure sensor enters deep-sleep.
Reliable Zigbee 3.0 sensors exist that provide true NDIR CO₂, humidity and temperature data and integrate smoothly with mainstream home-automation hubs. Prioritise NDIR technology, proper calibration, and good mesh design for dependable, accurate indoor-air-quality monitoring.